Design Model to Operating Model: A Snowdon Towers Case Study
How much of an operating platform can Revit define?
Autodesk's Snowdon Towers sample models were normalized, checked, repaired in copies, loaded into Autodesk Tandem and read back. The question is how fully assets, systems and traces can be defined in Revit with QC and repair tools, so that Tandem or any other operating platform needs less work. The steps, results and estimated effort follow. What to turn over is the reader's decision.
Scope: the settled process, with technical issues resolved. Development and troubleshooting are left out of the steps and the estimates.
Before and after, on the same building
Both views show the same asset list and share one camera. Drag to turn, scroll with Ctrl held to zoom, and select an item to trace what feeds it and what it feeds.
Systems and traces, defined in Revit
HVAC, fully. Plumbing, all but eight of 71 systems. Electrical, every circuit item. All 148 HVAC systems now have a unique name, a tagged source, their terminals, and every part marked with its system, role and flow direction. One HVAC and one hot water system were then made in Tandem, each from a single field, and both traces matched.
| In the Revit models | As authored | After QC and repair |
|---|---|---|
| Systems with a unique name to the standard | 0 of 219 | 217 |
| Systems whose source is set to a tagged asset | 0 | 213 |
| Systems that reach a terminal | 219 | 219 |
| All three | 0 | 211 |
| HVAC systems with their equipment as a marked member | 0 of 148 | 148 |
| Plumbing systems with their equipment as a marked member | 0 of 71 | 63 |
| HVAC and Plumbing parts carrying system, role and flow | 0 | 8,752 |
| Electrical items carrying system, circuit and path | 0 | 1,405 |
The connections were already in the models: all 219 systems reached a terminal before any repair. QC added identity, sources and direction.
Why a system name is not enough
A Tandem system is one parameter, one value and a distance tolerance. Revit gives a unit that serves four systems one combined name, RA-31,SA-31,EA-31,OA-31, so it cannot be selected with any of them. All 37 heat recovery units are like this. BDS now writes one field per service on every part.
| Field | Unit SNT-L05-HRU-002 | Its supply grilles | Its outdoor cap |
|---|---|---|---|
| BDS_System_SA | SA-31 | SA-31 | |
| BDS_System_OA | OA-31 | OA-31 | |
| BDS_SystemRole | SA:source; OA:source, and two more | SA:terminal | OA:terminal |
| BDS_SystemFlow | SA:from source; OA:to source, and two more | SA:from source | OA:to source |
Where the method stops in Plumbing
| Systems | Defined | With source | What is missing |
|---|---|---|---|
| Heater exhaust | 31 of 31 | 31 | |
| Hot water | 32 of 32 | 31 | One network is not connected to a heater |
| Cold water | 5 of 5 | 0 | No source is set, and none of the five is one connected network |
| Sanitary | 1 of 1 | 1 | Two pieces, with a 0.28 ft overlap to resolve |
| Roof and parking drainage | 0 of 2 | 2 | The standard has no name for storm drainage |
Members of the six systems with no source still carry their system and role. Their flow field reads no source, so nothing claims a direction the model can't support. All of these are decisions for the owner, designer or modeler.
Electrical, where the trace is the data
Wiring is seldom modeled as touching parts, so geometry can't carry a circuit's path. The circuits can. A panel is a load of its feeder and the source of its branches, so BDS writes distribution, branch and PV as separate services, plus the circuit name and the whole path as text.
| In the Electrical copy | Result |
|---|---|
| Items on a circuit that carry the fields | 1,405 of 1,405 |
| Circuit links that can be rebuilt from the fields alone | 1,397 of 1,397 |
| Paths equal to the raw circuits, climbed independently | 1,292 of 1,292 |
| Distribution, from one switchboard | 47 boards |
| Branch systems, one for each panel | 36 |
| PV modules, in the seven boards they feed | 113 |
One path, on a panel's lights and outlets: SNT-P01-SWB-001 > SNT-P01-EM-006 > SNT-P01-EM-007 > SNT-L05-PNL-005. Any platform that reads properties can follow it without a drawing.
- The links were read from Revit's circuits. QC did not create them.
- The 37 heat recovery units are in another model. Their power connections in this model carry the path; the units themselves do not yet.
- In Tandem, one panel was made from its field: 36 members, all matching BDS by ID and all standalone. There is no geometry to trace.
- A path shows how a building is powered. The sample standard restricts distribution equipment, so an owner should decide who receives these fields.
Connections that only look connected
A pipe or duct drawn up to a unit by eye can look finished when the family has no connector there. Then the system has no source and cannot be traced in Revit. QC now compares each open end, and each capped end, with the surface of nearby equipment. CONT-006 names the equipment and the likely reason.
| Fault placed in a spare copy | Result |
|---|---|
| Pipe on a heat recovery unit, or duct on a vanity: no connector of that kind | Found, 2 of 2 |
| The same, stopping 0.5 in short | Found, 2 of 2 |
| The same, 0.2 ft inside the equipment | Found, 2 of 2 |
| Duct on a unit whose duct connectors are all in use | Found, 1 of 1 |
| Stopping 3 in short, beyond the 1 in tolerance | Ignored, 2 of 2 |
| HVAC and Plumbing copies with nothing seeded | 0 reported |
The faults were seeded because none were found in the two models. The check reports and changes nothing. Adding a connector to a family is a possible next repair; it affects every instance, so it needs approval. Caps, wrong sizes or services, and families with no solid have not been seen in Revit yet.
The same system made three ways in Tandem
| By Revit system name | By System Class, then split | By the BDS field | |
|---|---|---|---|
| Setup | One system | One system, two subsystems | One system |
| Physical parts in SA-31 | 39 | 39, unit in another subsystem | 40, the same 40 as BDS |
| Heat recovery unit in it | No | Apart | Yes |
| Trace from the unit | No unit to start from | 9 terminals and 1 outdoor cap | 9 terminals |
| Outdoor air kept apart from supply | Yes | No | Yes |
The untouched models were later loaded into a second facility. By name they gave the same 39 parts, and a trace could run between grilles but not from the unit. So the connections came with the model. What QC added is the identity that puts the unit in and makes one field enough.
Tandem also lists 30 center lines in the system, as it did by name. The new HVAC copy was updated in place in Tandem.
A hot water system, checked the same way
Water heater SNT-L05-WH-003 is in three systems: hot water, cold water and exhaust. A Tandem system made from BDS_System_DHW = DHW-29 held 63 physical parts, the same 63 as BDS, heater included, plus 57 center lines. The trace from the heater reached its five fixtures and nothing from the other two systems.
What still has to happen outside Revit
- Each system still has to be created once in Tandem. Here that was done by hand.
- Tandem draws its trace from geometry. It does not read the role and flow fields; other platforms can use them without geometry.
- Electrical relies on the fields. A platform has to read them, since there is no geometry to trace.
- The button version is built; the results here came from its unattended version.
- Three were checked in Tandem: one HVAC system, one hot water system and one panel. The other 215 HVAC and plumbing systems and 35 panels were not.
- The same three were made from the untouched models in a second facility: 39 of 40, 57 of 63 and 35 of 36 parts. Each missed its source, and hot water its five fixtures. Those three are not a measure of the whole building.
Replay: the original beside the result
The same three systems, step by step. The left scene is Autodesk's untouched Revit model. The right is the copy after QC and repair. Both are drawn from what Revit holds in each file, and no part moved. This is a replay of the data, not Tandem's viewer.
Drag either scene to turn both. Scroll with Ctrl held to zoom. The selections on the left were then made in Tandem from the untouched models, and the counts matched: 39, 57 and 35 parts. The recorded tour shows them.
Recorded tour: the same steps in two Tandem facilities
Stills from two live facilities on November 25, 2026, in order. One holds Autodesk's untouched models, the other the repaired copies. It is a recording, so no account is needed. Systems in the original use Revit's own system or panel name, since it has no BDS fields. Its main model is Architectural rather than Electrical, so the buildings are drawn differently. In the repaired facility, the supply air and hot water forms were filled in again afterward for a clear picture, then cancelled.
One value makes the system, and the trace runs from the heat recovery unit to its nine grilles.
Create one system


Steps and actions
Receive and protect the models
Copy all seven models, record a hash of each original, work only in copies.
Uses Scripted copy
Result Originals unchanged, confirmed by hash
Set the owner standard
Adapt classes, required fields, naming rules, tolerances and expected points per class.
Uses BDS Standards, agent draft
Result One standard file that every tool reads
Extract
Run every model without opening the Revit window. Read elements, rooms, systems, circuits and connectors.
Uses BDS headless extract
Result 3,429 elements in under two minutes of model time
Normalize and check
Give each item a stable ID and unique tag, class it, merge duplicates, join rooms across linked models, trace feeds, convert units.
Uses BDS normalize and QC
Result 2,629 assets, 579 duplicates marked, 20,744 values in consistent units
Close gaps with an agent
Propose classes, links and expected points the rules cannot reach. Mark each as model, derived or proposed.
Uses Agent, reviewed by a person
Result 3,758 links in the release, 353 expected points, 45 proposals held out
Review rooms
Compare every room with Tandem and with Revit, then accept, reject or hold each difference.
Uses BDS compare, agent evidence
Result 99.4% agreement where both name a room; 85 rooms added, nine held for a person
Write back and repair
Write IDs, tags and classes into copies. Set sources, names and levels. Save, reopen and compare.
Uses BDS optimize
Result 24,003 field checks matched; element IDs and positions unchanged
Define systems
Write system, role and flow on every part, one field per service. Check them against the model.
Uses BDS Define Systems, SYS-020
Result 217 of 219 HVAC and Plumbing systems defined, 211 with their equipment; no conflicts
Load Tandem
Set the template and classes, import models, match on IFC GUID, write assets, create streams, read back.
Uses BDS loader, Tandem Data API
Result 396 assets and 353 streams, every value the same on readback
Update in place
Replace the models with the repaired copies. Compare snapshots before and after.
Uses Tandem Update, BDS snapshot
Result 28,149 element keys kept; 2,616 assets carry their own data
Test the data path
Send a labelled simulated day, read it back, compare every value.
Uses BDS simulate, Tandem Data API
Result 1,358 of 1,358 readings match on 14 streams
Report
Publish coverage, open items and the dataset.
Uses BDS exports, agent draft
Result Tables, SQLite, Brick, Haystack and a viewer
Screens from the work
Unretouched captures, cropped to leave out account details and file paths.











Coverage by stage
QC before and after
Findings on assets and systems for the main rules, with one standard, from reopening the untouched models and then the saved copies.
| Check | Rule | As authored | Optimized copy |
|---|---|---|---|
| Assets with no class in the standard | CL-001, CL-002 | 2,629 | 0 |
| Assets missing a required field | REQ-002 | 2,629 | 0 |
| Assets with no level | SP-002 | 160 | 6 |
| Systems with no source equipment | SYS-011 | 179 | 0 |
| System naming findings | NM rules | 219 | 2 |
| Assets with no room | SP-001 | 362 | 362 |
| Assets with open connections | CONT-001 | 121 | 121 |
| Assets with unassigned connectors | SYS-010 | 119 | 119 |
| Split or overlapping systems | CONT-003, 004 | 9 | 9 |
| Flow comparisons to review | FLOW-003 | 0 | 37 |
| IFC class to review | IFC-001 | 0 | 71 |
| Equipment beyond network reach | NET-001 | 0 | 21 |
| Assets in classes to complete | SEM-001 | 0 | 23 |
Some checks can only run once sources, classes and points exist, so the last four begin at zero.
What the tools now do
Normalization and QC functions used in this run.
| Duplicate check | Finds the same item modeled in two disciplines and tags it once |
| Circuit links | Reads switchboard to meter bank to panel to load: 1,197 of 1,397 power links without an agent |
| Linked rooms | Finds rooms in the architectural model, including tall rooms and slabs |
| Cross-model feeds | Joins equipment to its supply in another model: 78 links exported |
| System direction and sources | Sets source equipment and keeps outdoor air and flues running the right way |
| Outlets and devices | Counts data outlets apart from network devices |
| Looks connected | Finds a duct or pipe end that sits on equipment but is not joined, and says why. Reports only |
| Define systems | Writes one field per service so a system, its equipment included, can be chosen by one value, and flags any part that falls out of date |
| Grouped elements | Writes tags to items inside model groups |
| Load, snapshot and readback | Writes to Tandem, then proves what it holds, element by element |
| Simulated readings | Sends, compares, repairs and removes labelled test data |
The same checks, inside Tandem
Every tenant space, traced to its meters
Simulated readings through Tandem
SIMULATED No building system feeds this sample. These values were made up, sent to Tandem on November 25, and read back through its Data API. Each is stored under a parameter named BDS Simulated Value.
One day on heat recovery unit SNT-L05-HRU-005, drawn from the readback. Shaded: the staged fault, 9 to 11 am. The filter alarm comes on, the supply fan stops and supply air cools. Local time.
Simulated readings as a table
| Time | Supply air temperature | Return air temperature | Supply fan status | Exhaust fan status | Filter alarm |
|---|---|---|---|---|---|
| Nov 24, 12:45 | 67.4 °F | 71.3 °F | On | On | Normal |
| Nov 24, 13:00 | 67.6 °F | 71.7 °F | On | On | Normal |
| Nov 24, 13:15 | 67.7 °F | 71.8 °F | On | On | Normal |
| Nov 24, 13:30 | 66.8 °F | 71.8 °F | On | On | Normal |
| Nov 24, 13:45 | 67.8 °F | 71.6 °F | On | On | Normal |
| Nov 24, 14:00 | 67.4 °F | 71.4 °F | On | On | Normal |
| Nov 24, 14:15 | 67.5 °F | 71.2 °F | On | On | Normal |
| Nov 24, 14:30 | 67.3 °F | 71.3 °F | On | On | Normal |
| Nov 24, 14:45 | 67.0 °F | 71.4 °F | On | On | Normal |
| Nov 24, 15:00 | 66.6 °F | 71.1 °F | On | On | Normal |
| Nov 24, 15:15 | 67.4 °F | 70.8 °F | On | On | Normal |
| Nov 24, 15:30 | 67.0 °F | 71.4 °F | On | On | Normal |
| Nov 24, 15:45 | 66.7 °F | 71.1 °F | On | On | Normal |
| Nov 24, 16:00 | 67.2 °F | 70.7 °F | On | On | Normal |
| Nov 24, 16:15 | 66.4 °F | 70.6 °F | On | On | Normal |
| Nov 24, 16:30 | 66.4 °F | 71.1 °F | On | On | Normal |
| Nov 24, 16:45 | 65.8 °F | 70.9 °F | On | On | Normal |
| Nov 24, 17:00 | 66.0 °F | 70.4 °F | On | On | Normal |
| Nov 24, 17:15 | 65.9 °F | 70.6 °F | On | On | Normal |
| Nov 24, 17:30 | 66.7 °F | 70.4 °F | On | On | Normal |
| Nov 24, 17:45 | 66.3 °F | 70.1 °F | On | On | Normal |
| Nov 24, 18:00 | 66.0 °F | 70.5 °F | On | On | Normal |
| Nov 24, 18:15 | 66.1 °F | 70.8 °F | On | On | Normal |
| Nov 24, 18:30 | 66.0 °F | 70.6 °F | On | On | Normal |
| Nov 24, 18:45 | 66.0 °F | 70.8 °F | On | On | Normal |
| Nov 24, 19:00 | 66.0 °F | 70.8 °F | On | On | Normal |
| Nov 24, 19:15 | 65.8 °F | 70.5 °F | On | On | Normal |
| Nov 24, 19:30 | 65.5 °F | 70.5 °F | On | On | Normal |
| Nov 24, 19:45 | 65.8 °F | 70.5 °F | On | On | Normal |
| Nov 24, 20:00 | 66.0 °F | 70.6 °F | On | On | Normal |
| Nov 24, 20:15 | 65.7 °F | 70.7 °F | On | On | Normal |
| Nov 24, 20:30 | 66.0 °F | 70.5 °F | On | On | Normal |
| Nov 24, 20:45 | 66.0 °F | 70.5 °F | On | On | Normal |
| Nov 24, 21:00 | 65.6 °F | 70.4 °F | On | On | Normal |
| Nov 24, 21:15 | 66.0 °F | 70.7 °F | On | On | Normal |
| Nov 24, 21:30 | 65.7 °F | 70.4 °F | On | On | Normal |
| Nov 24, 21:45 | 66.0 °F | 70.4 °F | On | On | Normal |
| Nov 24, 22:00 | 66.0 °F | 70.6 °F | On | On | Normal |
| Nov 24, 22:15 | 66.3 °F | 70.5 °F | On | On | Normal |
| Nov 24, 22:30 | 65.7 °F | 70.8 °F | On | On | Normal |
| Nov 24, 22:45 | 66.2 °F | 70.5 °F | On | On | Normal |
| Nov 24, 23:00 | 65.6 °F | 70.4 °F | On | On | Normal |
| Nov 24, 23:15 | 65.5 °F | 70.8 °F | On | On | Normal |
| Nov 24, 23:30 | 66.4 °F | 70.5 °F | On | On | Normal |
| Nov 24, 23:45 | 66.1 °F | 70.7 °F | On | On | Normal |
| Nov 25, 00:00 | 65.4 °F | 70.2 °F | On | On | Normal |
| Nov 25, 00:15 | 66.1 °F | 70.7 °F | On | On | Normal |
| Nov 25, 00:30 | 65.7 °F | 70.6 °F | On | On | Normal |
| Nov 25, 00:45 | 66.0 °F | 70.4 °F | On | On | Normal |
| Nov 25, 01:00 | 66.3 °F | 70.5 °F | On | On | Normal |
| Nov 25, 01:15 | 66.3 °F | 70.3 °F | On | On | Normal |
| Nov 25, 01:30 | 66.0 °F | 70.5 °F | On | On | Normal |
| Nov 25, 01:45 | 65.7 °F | 70.6 °F | On | On | Normal |
| Nov 25, 02:00 | 65.9 °F | 70.8 °F | On | On | Normal |
| Nov 25, 02:15 | 66.2 °F | 70.6 °F | On | On | Normal |
| Nov 25, 02:30 | 66.4 °F | 70.5 °F | On | On | Normal |
| Nov 25, 02:45 | 65.5 °F | 70.7 °F | On | On | Normal |
| Nov 25, 03:00 | 66.2 °F | 70.7 °F | On | On | Normal |
| Nov 25, 03:15 | 66.3 °F | 70.5 °F | On | On | Normal |
| Nov 25, 03:30 | 65.4 °F | 70.5 °F | On | On | Normal |
| Nov 25, 03:45 | 65.9 °F | 70.4 °F | On | On | Normal |
| Nov 25, 04:00 | 66.0 °F | 70.5 °F | On | On | Normal |
| Nov 25, 04:15 | 66.2 °F | 70.6 °F | On | On | Normal |
| Nov 25, 04:30 | 66.3 °F | 70.6 °F | On | On | Normal |
| Nov 25, 04:45 | 65.6 °F | 70.1 °F | On | On | Normal |
| Nov 25, 05:00 | 66.2 °F | 69.9 °F | On | On | Normal |
| Nov 25, 05:15 | 66.0 °F | 70.3 °F | On | On | Normal |
| Nov 25, 05:30 | 66.0 °F | 70.7 °F | On | On | Normal |
| Nov 25, 05:45 | 65.5 °F | 70.5 °F | On | On | Normal |
| Nov 25, 06:00 | 65.9 °F | 70.4 °F | On | On | Normal |
| Nov 25, 06:15 | 66.0 °F | 70.4 °F | On | On | Normal |
| Nov 25, 06:30 | 66.1 °F | 70.4 °F | On | On | Normal |
| Nov 25, 06:45 | 66.3 °F | 70.5 °F | On | On | Normal |
| Nov 25, 07:00 | 66.2 °F | 70.4 °F | On | On | Normal |
| Nov 25, 07:15 | 66.5 °F | 70.7 °F | On | On | Normal |
| Nov 25, 07:30 | 66.8 °F | 70.8 °F | On | On | Normal |
| Nov 25, 07:45 | 66.5 °F | 71.1 °F | On | On | Normal |
| Nov 25, 08:00 | 66.6 °F | 71.1 °F | On | On | Normal |
| Nov 25, 08:15 | 66.5 °F | 71.1 °F | On | On | Normal |
| Nov 25, 08:30 | 67.0 °F | 71.0 °F | On | On | Normal |
| Nov 25, 08:45 | 67.4 °F | 71.1 °F | On | On | Normal |
| Nov 25, 09:00 | 61.4 °F | 71.2 °F | Off | On | Alarm |
| Nov 25, 09:15 | 61.1 °F | 71.1 °F | Off | On | Alarm |
| Nov 25, 09:30 | 60.8 °F | 71.2 °F | Off | On | Alarm |
| Nov 25, 09:45 | 61.5 °F | 71.3 °F | Off | On | Alarm |
| Nov 25, 10:00 | 61.5 °F | 71.6 °F | Off | On | Alarm |
| Nov 25, 10:15 | 61.6 °F | 71.3 °F | Off | On | Alarm |
| Nov 25, 10:30 | 61.1 °F | 71.1 °F | Off | On | Alarm |
| Nov 25, 10:45 | 61.3 °F | 71.8 °F | Off | On | Alarm |
| Nov 25, 11:00 | 67.4 °F | 71.2 °F | On | On | Normal |
| Nov 25, 11:15 | 67.2 °F | 71.5 °F | On | On | Normal |
| Nov 25, 11:30 | 67.7 °F | 71.2 °F | On | On | Normal |
| Nov 25, 11:45 | 67.4 °F | 71.5 °F | On | On | Normal |
| Nov 25, 12:00 | 67.4 °F | 71.4 °F | On | On | Normal |
| Nov 25, 12:15 | 67.7 °F | 71.3 °F | On | On | Normal |
| Nov 25, 12:30 | 67.0 °F | 71.8 °F | On | On | Normal |
| Nov 25, 12:45 | 66.8 °F | 71.2 °F | On | On | Normal |
- 1,358 of 1,358 readings match. 14 streams, every 15 minutes for a day, across the unit, its apartment's water heater and meters, a refrigerator, the PV inverter and a battery.
- Acceptance is by readback. Every reading is read out of Tandem and compared with what was sent.
- The chart is drawn from the readback and is not a Tandem screen. These streams have no class, and Tandem's own charts showed no data for them.
Estimated hours and tokens
Estimates for repeating this run on a building this size with the tools in place. They are not timed. Person hours cover decisions, review and work in Revit and Tandem. Machine hours cover tools and agents, and can overlap.
| Step | Person hours | Machine hours | Output tokens, thousands | New input tokens, thousands |
|---|---|---|---|---|
| 1. Receive and protect the models | 0.5 to 1 | 0.1 to 0.2 | 2 to 4 | 10 to 20 |
| 2. Set the owner standard | 8 to 16 | 0.5 to 1 | 20 to 35 | 60 to 100 |
| 3. Extract | 0.5 to 1 | 0.1 to 0.2 | 3 to 5 | 10 to 20 |
| 4. Normalize and check | 4 to 8 | 0.5 to 1 | 15 to 25 | 50 to 90 |
| 5. Close gaps with an agent | 6 to 12 | 0.5 to 1 | 20 to 35 | 60 to 110 |
| 6. Review rooms | 2 to 4 | 0.2 to 0.4 | 8 to 12 | 25 to 45 |
| 7. Write back and repair | 6 to 12 | 0.5 to 1 | 20 to 30 | 60 to 100 |
| 8. Define systems | 2 to 4 | 0.2 to 0.4 | 6 to 10 | 20 to 35 |
| 9. Load Tandem | 3 to 5 | 0.3 to 0.5 | 10 to 15 | 30 to 50 |
| 10. Update in place | 2 to 3 | 0.2 to 0.4 | 6 to 10 | 20 to 35 |
| 11. Test the data path | 1.5 to 3 | 0.2 to 0.4 | 8 to 14 | 25 to 45 |
| 12. Report | 2 to 4 | 0.3 to 0.6 | 15 to 25 | 40 to 65 |
| All steps | 37.5 to 73 | 3.6 to 7.1 | 133 to 220 | 410 to 715 |
- Tokens follow decisions more than assets. The tools read the models and tables. The agent reads summaries, exceptions and files it edits, so a larger building with the same standard need not use tokens in proportion.
- Where the token range comes from. The session log for November 24 and 25 shows about 511,000 output tokens, 1.7 million new input tokens and 141 million tokens reread from cache. That includes development, troubleshooting and writing pages. The estimate is a share of it, split by step.
- Cached rereads are separate. Each step sends the conversation again, mostly from cache. One long session made that number large; a fresh session per step would cut it.
- The log's active time was about 4.4 hours across those two days, with each pause counted as five minutes at most. It does not measure a person's review time.
- Left out: real point mapping, manufacturer and serial data, field work, hardware, licenses, tool development and building a standard from nothing.
Decide what to turn over
What this run showed, and what each item needs before it can be a deliverable on a real project.
| Deliverable | In this run | Needs |
|---|---|---|
| Asset list with stable IDs, tags and classes | Shown | Owner and engineer accept the proposed classes |
| Rooms and levels | Shown for most | A person places the items with no room |
| Feeds and serves links | Shown for most | Engineer reviews derived links; 45 proposals stay out |
| System membership, role and flow | Shown for HVAC, Plumbing and Electrical | A person settles eight Plumbing systems; owner decides who sees electrical paths |
| Systems and traces in the twin | Three systems, two traces | Create each system once |
| Expected point list | Shown for 126 assets | Controls contractor confirms each point |
| Tandem or other twin, loaded and read back | Shown for 396 assets | Plan size and access rights |
| Repaired models | Shown in copies | Design team accepts changes and resolves open findings |
| Readings through the twin | Shown with simulated data | Real control system, gateways and security approval |
| Manufacturer and model | Not in the models | Submittals |
| Serial, install date, warranty | Not in the models | Startup forms or field capture |
| Test and balance, functional test results | Not in the models | Commissioning records |
| As-built condition | Not in the models | Field verification |
Basis
- Autodesk sample design models, Revit 2025. There is no control system and no as-built record.
- All readings were simulated. The agent's classes and points are proposals.
- Tandem's free plan limited the load to 396 of 2,629 assets. The models carry tags and classes for 2,616.
- One building, one run. Real projects are messier.
Run November 24 and 25, 2026.